Plant automation, fire and gas, digital fire clock
Complete LPG plant automation plus the full fire and gas system, executed in about five months.
- Fire and gas
- ROV control
- Zone annunciation
Upgrade of the fire and gas automation at the HPCL LPG bottling plant.
HPCL wanted the fire and gas automation at its LPG bottling plant in Visakhapatnam upgraded to the OISD-STD-144 deluge and fire water arrangement.
Detection loops trigger the area deluge valve; ring main pressure drop starts fire engines in sequence; a jockey pump keeps the main above about 7 bar, to OISD-STD-144.
Detection loops in each area trigger that area's deluge valve. Water sprays from the pressurised ring main, and the pressure drop starts the fire engines in a set sequence.
A jockey pump keeps the ring main above about 7 bar, compensating for leakage, so water is available the instant a deluge valve opens.
The SCADA shows fire engine status with run hours and counters for each pump.

Complete LPG plant automation plus the full fire and gas system, executed in about five months.

PLC and SCADA for the augmented gas receiving and metering station that supplies the cement plant and its power plant.

Upgrade of the dispatch terminal at the head of the Vizag to Secunderabad LPG pipeline from another PLC make to GE, in a fully redundant configuration.
Tell us what you are planning, even if the details are still rough. We reply with a technical approach and an offer.